BF24-SR-T
Привод BELIMO BF24-SR-T
0,00 ₽
Цена с НДС
Описание
Описание
Mode of operation
The actuator is controlled with a standard signal of DC 0 ... 10 V and moves the damper to the operating position while tensioning the return spring at the same time. The damper is turned back to the safety position by spring energy when the supply voltage is interrupted.
Thermoelectric tripping device
If the ambient temperature of 72°C is exceeded, the thermal fuse Tf1 responds.
If the duct inside temperature of 72°C is exceeded, the exchangeable thermal fuse Tf2/Tf3 will respond.
When the thermal fuses Tf1, Tf2 or Tf3 respond, the supply voltage is interrupted permanently and irreversibly.
The LED is lit when
– there is a supply voltage,
– the temperature fuses are OK and
– the test switch is not pressed.
The function of the thermal fuse and the test button is only warranted if the actuator is connected to the power supply and has reached its operating position (LED on).
Signalling
Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions.
The position of the damper blade can be read off on a mechanical position indicator.
Manual operation
Without power supply, the damper can be operated manually and fixed in any required position. It can be unlocked manually or automatically by applying the supply voltage. If manual operation is used when supply voltage is present, the actuator first moves to the safety position for checking and then to the position as defined by positioning signal Y. During this self-check, the motor running time is increased to 100 s and the measuring voltage remains at 2 V.
Характеристики
Технические характеристики
Electrical data
Nominal voltage
AC/DC 24 V
Nominal voltage frequency
50/60 Hz
Nominal voltage range
AC 19.2 V ... 28.8 V / DC 21.6 V ... 28.8 V
Power consumption in operation
7 W
Power consumption at rest
2 W
Power consumption for wire sizing
9.5 VA
Power consumption for wire sizing note
Imax 8.3 A @ 5 ms
Auxiliary switch
2 x SPDT
Switching capacity auxiliary switch
Contact gold-plated silver: 1 mA … 3 (0.5) A, DC 5 V … AC 250 V (II Totally insulated)
Switching points auxiliary switch
5° / 80°
Connection supply / control
Cable 1 m, 4 x 0.75 mm (halogen-free)
Connection auxiliary switch
Cable 1 m, 6 x 0.75 mm (halogen-free)
Cable length thermoelectric tripping device
1 m
Functional data
Torque motor
Min. 18 Nm
Torque spring-return
Min. 12 Nm
Control signal Y DC
0 V ... 10 V
Control signal Y note
Input impedance 100 k (0.1 mA)
Operating range Y DC
2 V ... 10 V
Operating range Y note
For control signal Y
Position feedback U DC
2 V ... 10 V
Position feedback U note
Max. 0.5 mA (for 0 … 100% angle of rotation)
Position accuracyn
±5%
Direction of rotation motor
Can be selected by mounting L / R
Angle of rotation
Max. 95°
Running time motor
‹120 s / 90°
Running time spring-return
16 s (tamb = 20°C)
Sound power level motor max.
45 dB (A)
Sound power level spring-return max.
63 dB (A)
Damper rotation
Form fit 12 mm (10 mm with enclosed adapter)
Position indication
Mechanically, with pointer
Service life
Min. 60,000 safety positions
Safety
Response temperature thermal fuse
Tf1: Duct outside temperature 72°C Tf2 and Tf3: Duct inside temperature 72°C
Protection class IEC/EN
III Safety extra-low voltage
Degree of protection IEC/EN
IP54 in all mounting positions
EMC
CE according to 2014/30/EU
Low-voltage directive
CE according to 2014/35/EU
Certification IEC/EN
Certified according to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation
Type 1.AA.B
Rated impulse voltage supply / control
0.8 kV
Control pollution degree
3
Ambient temperature normal duty
-30°C … 50°C
Ambient temperature safety duty T
he safety position will be attained up tomax. 75°C
Non-operating temperature
-40°C ... 50°C
Ambient humidity
95% r.h., non-condensing
Maintenance
Maintenance-free
Weight
Weight
approx. 2.8 kg
Отзывы
Задать вопрос
Вы можете задать любой интересующий вас вопрос по товару или работе магазина.
Наши квалифицированные специалисты обязательно вам помогут.
Mode of operation
The actuator is controlled with a standard signal of DC 0 ... 10 V and moves the damper to the operating position while tensioning the return spring at the same time. The damper is turned back to the safety position by spring energy when the supply voltage is interrupted.
Thermoelectric tripping device
If the ambient temperature of 72°C is exceeded, the thermal fuse Tf1 responds.
If the duct inside temperature of 72°C is exceeded, the exchangeable thermal fuse Tf2/Tf3 will respond.
When the thermal fuses Tf1, Tf2 or Tf3 respond, the supply voltage is interrupted permanently and irreversibly.
The LED is lit when
– there is a supply voltage,
– the temperature fuses are OK and
– the test switch is not pressed.
The function of the thermal fuse and the test button is only warranted if the actuator is connected to the power supply and has reached its operating position (LED on).
Signalling
Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions.
The position of the damper blade can be read off on a mechanical position indicator.
Manual operation
Without power supply, the damper can be operated manually and fixed in any required position. It can be unlocked manually or automatically by applying the supply voltage. If manual operation is used when supply voltage is present, the actuator first moves to the safety position for checking and then to the position as defined by positioning signal Y. During this self-check, the motor running time is increased to 100 s and the measuring voltage remains at 2 V.
Характеристики
Технические характеристики
Electrical data
Nominal voltage
AC/DC 24 V
Nominal voltage frequency
50/60 Hz
Nominal voltage range
AC 19.2 V ... 28.8 V / DC 21.6 V ... 28.8 V
Power consumption in operation
7 W
Power consumption at rest
2 W
Power consumption for wire sizing
9.5 VA
Power consumption for wire sizing note
Imax 8.3 A @ 5 ms
Auxiliary switch
2 x SPDT
Switching capacity auxiliary switch
Contact gold-plated silver: 1 mA … 3 (0.5) A, DC 5 V … AC 250 V (II Totally insulated)
Switching points auxiliary switch
5° / 80°
Connection supply / control
Cable 1 m, 4 x 0.75 mm (halogen-free)
Connection auxiliary switch
Cable 1 m, 6 x 0.75 mm (halogen-free)
Cable length thermoelectric tripping device
1 m
Functional data
Torque motor
Min. 18 Nm
Torque spring-return
Min. 12 Nm
Control signal Y DC
0 V ... 10 V
Control signal Y note
Input impedance 100 k (0.1 mA)
Operating range Y DC
2 V ... 10 V
Operating range Y note
For control signal Y
Position feedback U DC
2 V ... 10 V
Position feedback U note
Max. 0.5 mA (for 0 … 100% angle of rotation)
Position accuracyn
±5%
Direction of rotation motor
Can be selected by mounting L / R
Angle of rotation
Max. 95°
Running time motor
‹120 s / 90°
Running time spring-return
16 s (tamb = 20°C)
Sound power level motor max.
45 dB (A)
Sound power level spring-return max.
63 dB (A)
Damper rotation
Form fit 12 mm (10 mm with enclosed adapter)
Position indication
Mechanically, with pointer
Service life
Min. 60,000 safety positions
Safety
Response temperature thermal fuse
Tf1: Duct outside temperature 72°C Tf2 and Tf3: Duct inside temperature 72°C
Protection class IEC/EN
III Safety extra-low voltage
Degree of protection IEC/EN
IP54 in all mounting positions
EMC
CE according to 2014/30/EU
Low-voltage directive
CE according to 2014/35/EU
Certification IEC/EN
Certified according to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation
Type 1.AA.B
Rated impulse voltage supply / control
0.8 kV
Control pollution degree
3
Ambient temperature normal duty
-30°C … 50°C
Ambient temperature safety duty T
he safety position will be attained up tomax. 75°C
Non-operating temperature
-40°C ... 50°C
Ambient humidity
95% r.h., non-condensing
Maintenance
Maintenance-free
Weight
Weight
approx. 2.8 kg
Отзывы
Задать вопрос
Вы можете задать любой интересующий вас вопрос по товару или работе магазина.
Наши квалифицированные специалисты обязательно вам помогут.
Характеристики
| Технические характеристики | Electrical dataNominal voltageAC/DC 24 VNominal voltage frequency50/60 HzNominal voltage rangeAC 19.2 V ... 28.8 V / DC 21.6 V ... 28.8 VPower consumption in operation7 WPower consumption at rest2 WPower consumption for wire sizing9.5 VAPower consumption for wire sizing noteImax 8.3 A @ 5 msAuxiliary switch2 x SPDTSwitching capacity auxiliary switchContact gold-plated silver: 1 mA … 3 (0.5) A, DC 5 V … AC 250 V (II Totally insulated)Switching points auxiliary switch5° / 80°Connection supply / controlCable 1 m, 4 x 0.75 mm (halogen-free)Connection auxiliary switchCable 1 m, 6 x 0.75 mm (halogen-free)Cable length thermoelectric tripping device1 mFunctional dataTorque motorMin. 18 NmTorque spring-returnMin. 12 NmControl signal Y DC0 V ... 10 VControl signal Y noteInput impedance 100 k (0.1 mA)Operating range Y DC2 V ... 10 VOperating range Y noteFor control signal YPosition feedback U DC2 V ... 10 VPosition feedback U noteMax. 0.5 mA (for 0 … 100% angle of rotation)Position accuracyn±5%Direction of rotation motorCan be selected by mounting L / RAngle of rotationMax. 95°Running time motor‹120 s / 90°Running time spring-return16 s (tamb = 20°C)Sound power level motor max.45 dB (A)Sound power level spring-return max.63 dB (A)Damper rotationForm fit 12 mm (10 mm with enclosed adapter)Position indicationMechanically, with pointerService lifeMin. 60,000 safety positionsSafetyResponse temperature thermal fuseTf1: Duct outside temperature 72°C Tf2 and Tf3: Duct inside temperature 72°CProtection class IEC/ENIII Safety extra-low voltageDegree of protection IEC/ENIP54 in all mounting positionsEMCCE according to 2014/30/EULow-voltage directiveCE according to 2014/35/EUCertification IEC/ENCertified according to IEC/EN 60730-1 and IEC/EN 60730-2-14Mode of operationType 1.AA.BRated impulse voltage supply / control0.8 kVControl pollution degree3Ambient temperature normal duty-30°C … 50°CAmbient temperature safety duty The safety position will be attained up tomax. 75°CNon-operating temperature-40°C ... 50°CAmbient humidity95% r.h., non-condensingMaintenanceMaintenance-freeWeightWeightapprox. 2.8 kg |
| Nominal voltage | AC/DC 24 V |
| Nominal voltage frequency | 50/60 Hz |
| Nominal voltage range | AC 19.2 V ... 28.8 V / DC 21.6 V ... 28.8 V |
| Power consumption in operation | 7 W |
| Power consumption at rest | 2 W |
| Power consumption for wire sizing | 9.5 VA |
| Power consumption for wire sizing note | Imax 8.3 A @ 5 ms |
| Auxiliary switch | 2 x SPDT |
| Switching capacity auxiliary switch | Contact gold-plated silver: 1 mA … 3 (0.5) A, DC 5 V … AC 250 V (II Totally insulated) |
| Switching points auxiliary switch | 5° / 80° |
| Connection supply / control | Cable 1 m, 4 x 0.75 mm (halogen-free) |
| Connection auxiliary switch | Cable 1 m, 6 x 0.75 mm (halogen-free) |
| Cable length thermoelectric tripping device | 1 m |
| Torque motor | Min. 18 Nm |
| Torque spring-return | Min. 12 Nm |
| Control signal Y DC | 0 V ... 10 V |
| Control signal Y note | Input impedance 100 k (0.1 mA) |
| Operating range Y DC | 2 V ... 10 V |
| Operating range Y note | For control signal Y |
| Position feedback U DC | 2 V ... 10 V |
| Position feedback U note | Max. 0.5 mA (for 0 … 100% angle of rotation) |
| Position accuracyn | ±5% |
| Direction of rotation motor | Can be selected by mounting L / R |
| Angle of rotation | Max. 95° |
| Running time motor | ‹120 s / 90° |
| Running time spring-return | 16 s (tamb = 20°C) |
| Sound power level motor max. | 45 dB (A) |
| Sound power level spring-return max. | 63 dB (A) |
| Damper rotation | Form fit 12 mm (10 mm with enclosed adapter) |
| Position indication | Mechanically, with pointer |
| Service life | Min. 60,000 safety positions |
| Response temperature thermal fuse | Tf1: Duct outside temperature 72°C Tf2 and Tf3: Duct inside temperature 72°C |
| Protection class IEC/EN | III Safety extra-low voltage |
| Degree of protection IEC/EN | IP54 in all mounting positions |
| EMC | CE according to 2014/30/EU |
| Low-voltage directive | CE according to 2014/35/EU |
| Certification IEC/EN | Certified according to IEC/EN 60730-1 and IEC/EN 60730-2-14 |
| Mode of operation | Type 1.AA.B |
| Rated impulse voltage supply / control | 0.8 kV |
| Control pollution degree | 3 |
| Ambient temperature normal duty | -30°C … 50°C |
| Ambient temperature safety duty T | he safety position will be attained up tomax. 75°C |
| Non-operating temperature | -40°C ... 50°C |
| Ambient humidity | 95% r.h., non-condensing |
| Maintenance | Maintenance-free |
| Weight | approx. 2.8 kg |